Thermal Imaging Fault Report - Contactor Terminations
|
|
|
|
Spot |
Temp |
Description |
|
Spot 1 |
87.4°C |
Blue Phase Load Cable Temp |
|
Spot 2 |
87.8°C |
Yellow Phase Load Cable Temp |
|
Spot 3 |
64.1°C |
Blue Phase Supply Cable Temp |
|
Spot 4 |
70.1°C |
Yellow Phase Supply Cable Temp |
|
Description |
Contactor cable terminations are hot, possibly due to sub-standard electrical contact and/or loading. |
|
Recommendation |
Inspect cable terminations for looseness, contaminant, corrosion, etc. Replace contactor as required. Re-terminate cables ensuring good electrical contact.Record actual and nominal load currents. If the load is excessive, investigate/remedy the cause. Upgrade cable as necessary. |
|
Priority |
This is a Priority 1 anomaly; it is recommended that remedial action should be taken urgently. |