Thermal Imaging Fault Report - Control Panel Main Isolator
|
|
|
|
Spot |
Temp |
Description |
|
Spot 1 |
81.1°C |
Yellow Phase Supply Cable Temp |
|
Spot 2 |
86.4°C |
Yellow Phase Load Cable Temp |
|
Spot 3 |
78.7°C |
Blue Phase Supply Cable Temp |
|
Spot 4 |
93.3°C |
Blue Phase Load Cable Temp |
|
Description |
Main Isolator cable terminations hot, possibly due to sub-standard electrical contact at the cable terminations and/or internal isolator contacts. |
|
Recommendation |
Inspect cable terminations for looseness, contaminant, corrosion, etc. Replace isolator as necessary and re-terminate cables ensuring good electrical contact. |
|
Priority |
This is a Priority 1 anomaly; it is recommended that remedial action should be taken urgently. |