Thermal Imaging Fault Report - Fuse Carrier Defect
|
|
|
|
Spot |
Temp |
Description |
|
Spot 1 |
41°C |
Y - Phase Fuse Carrier |
|
Spot 2 |
66°C |
B - Phase Fuse Carrier |
|
Dt1 |
25°C |
Temp Dif. (Sp2 - Sp1) |
|
Description |
Blue Phase fuse carrier is warm possibly due to sub-standard contact between fuse and fuse carrier interface. |
|
Recommendation Given |
Inspect fuse carrier/holder sprung contacts. Clean, repair or replace as necessary. |
|
Priority |
This is the main fuse to the building, failure would result in considerable production downtime. Due to the temperatures recorded, remedial work should be scheduled for the earliest opportunity. |